Embedded WorksTrackingForLessSensorWorks

Monnit MNS-9-AN-W2-LD Wireless Voltage Meter - 0-1.2 VDC - AA Battery / Grade: Commercial

Wireless Voltage Meter - 0-1.2 VDC



MSRP $74.00 - Save $0.00 (0.00%)
Buy MoreSave More
100+Need volume? - Get Quote
Monnit wireless voltage meters are capable of measuring the voltage off another device, battery, or sensor. This sensor is capable of measuring voltage up to 1.2 volts DC by connecting the leads on the sensor to the positive and ground terminals of the device being measured. Examples of interfacing devices include, but are not limited to: Strain Gauge, Pressure Transducer, RTD, Thermistor, or Thermocouple, Piezo Electric sensors, Photoresistor, Industrial Accelerometer, any kind of variable resistor, any kind of sensor that outputs a voltage, etc. If the device being measured is passive, the user must supply their own excitation voltage, as the Monnit wireless voltage meter is really just a voltage observer. Cannot be used for AC voltage measurement.

WARNING: Use caution when interfacing to the Monnit Wireless Voltage Meter. Negative voltages, any kind of AC Voltages, or DC Voltage exceeding 3.6V WILL DAMAGE the electronics of the Monnit Wireless Sensor. Monnit is not responsible for troubleshooting, replacing or reimbursing damages incurred by disregarding this warning.

Product Features
  • 900 MHz Operating Frequency
  • 2 Replaceable AA 1.5 V Batteries
  • 250 - 300 ft. non-line-of-sight device range*
  • At 1 hour heartbeat setting, included AA batteries will last more than 4 Years. **
  • FCC and IC certified.
  • Interfaces with other devices up to 1.2 VDC
  • Mounting flanges for easy securement
  * Actual range may vary depending on environment.
** Battery life is determined by sensor reporting frequency and other variables.
Power2 Replaceable AA 1.5V batteries
Battery LifeAt 1 hour heartbeat setting, included AA batteries will last more than 4 Years.
CertificationsComplies with Part 15 of the FCC Rules. (FCC ID: ZTL-RFSC1)
Complies with Industry Canada standards. (IC: 9794A-RFSC1)
Maximum Operating TemperaturesAA Alkaline: -18 to 55C (0 to 130F) AA Lithium: -40 to 85C (-40 to 185F)
Device Range250 - 300 ft. non-line-of-sight device range
Device SpecificationsAnalog Voltage Input Specifications
Max Operating Temperature Using AA Alkaline: -18 to 55C (0 to 130F)
Max Operating Temperature Using AA Lithium: -40 to 85C (-40 to 185F)
Optimal Battery Operating Temperature: +10C to +50C (+50F to +122F)
Maximum Rated Input Voltage: Up to 1.2 VDC
Dimensions4.375 in x 2.470 in x 1.111 in
ApplicationsAppliance monitoring
Line power monitoring
Power coupling monitoring
Power supply monitoring
Sump pump monitoring
Enclosure MaterialABS
Operating Frequency900Mhz (N. America)
Packing ListWireless Sensor
Mounting Tape
AA Batteries
Search in Results:
  • Show
  • Per Page